Network monitoring and visibility¶
An OT environment where events are not recorded has no forensic baseline. Volt Typhoon’s activity left minimal forensic trace in OT-adjacent networks in part because process creation auditing was not enabled: the logs that would have captured lateral movement commands were never written. Visibility in OT starts with understanding what is present on the network, followed by what it is doing, and is constrained throughout by the sensitivity of many OT devices to active interrogation.
Passive monitoring¶
Active network scanning is the standard discovery technique in IT security. In OT it carries real risk: a scan packet reaching a PLC or RTU that does not handle unexpected traffic gracefully can interrupt control execution. Many OT devices have been observed to reset or drop sessions on receiving a port scan from an unknown host.
Passive monitoring collects traffic from a network tap or span port without generating any packets of its own. On a passive sensor, the monitoring system sees every frame that crosses the monitored segment; no device knows it is being observed. This is the baseline technique for OT network visibility precisely because it generates no traffic of its own.
Commercial OT monitoring platforms, including Dragos, Claroty, Nozomi Networks, and Forescout OT, operate passively by default. They decode OT protocol traffic and extract process variable reads, writes, configuration changes, and authentication events from the packet stream, producing a record of what the network carried without touching any of the devices on it.
Asset inventory¶
Many OT environments do not have a current asset inventory. Equipment is added during expansions and modifications; retirements are sometimes incomplete; vendor-installed devices appear on the network without being formally registered. The first output of passive monitoring on a new segment is frequently a surprise: devices the operator did not know were present, running protocols the team had not identified.
Passive discovery builds an inventory from the traffic itself. A device that communicates appears in the inventory; its protocol, firmware version where the protocol carries it, and communication partners are derived from observation. The inventory degrades over time if not maintained; devices that stop communicating disappear from the observed traffic without any record of their absence.
A physical walkdown against the passively-built inventory is the validation step. Assets present physically but absent from the network inventory are powered off, isolated, or not yet communicating. Assets appearing in traffic but absent from the physical inventory warrant investigation.
Protocol-level visibility¶
OT protocol traffic carries information that generic network monitoring does not surface. A Modbus write to a specific register address, an IEC 104 C_SC_NA_1 command to a specific information object, an OPC UA write to a named process variable: these are events with specific process meaning. A generic flow monitor sees a TCP session on port 502; an OT-protocol-aware monitor sees a setpoint change on a specific output.
Protocol-level visibility makes the detection of anomalous commands possible: a write function code from an unexpected source address, a trip command outside a known maintenance window, a new device appearing in GOOSE multicast traffic. These are the signals that network-layer monitoring alone cannot generate, and they are the class of signal that would have detected the FrostyGoop Modbus writes and the Sandworm IEC 104 sessions that preceded the Ukrainian grid events.
Log collection¶
OT devices vary considerably in what they log and whether they expose logs externally. Modern PLCs and RTUs commonly support syslog forwarding. Older devices may have local event logs accessible only through their engineering software, or no logging capability at all. Engineering workstations running Windows generate event logs including process creation, logon events, and file access; these are collectable and carry significant detection value.
The DMZ staging pattern from the IT/OT boundary page applies to log collection: log collectors in the DMZ receive forwarded events from OT systems; the SIEM consumes from the DMZ collectors rather than polling OT systems directly. This avoids creating inbound connections from the IT network into OT and keeps the collection architecture consistent with the boundary design.
Windows Event ID 4688 logs process creation with command-line arguments when process auditing is enabled, a setting that is off by default. Volt Typhoon operated primarily through Windows built-in utilities; in environments where 4688 was not enabled, there was no record of what commands ran, with what arguments, or in response to what. Process auditing on OT-adjacent Windows systems is among the lower-cost improvements available; its absence was a recurring finding in the affected environments.
The detection baseline¶
Detection requires a baseline: a defined picture of normal that makes anomalous events visible. An OT network where no baseline has been established cannot reliably distinguish a Sandworm IEC 104 session from a legitimate control session, because both look like a TCP connection on port 2404 completing the STARTDT handshake.
Building the baseline takes time. A passive monitor on a new segment commonly spends weeks learning which devices communicate with which, on which protocols, at what cadence, carrying what types of commands. Alerts generated against an immature baseline produce false positives that erode operator trust in the monitoring system. The baseline is also a living document: process changes, equipment additions, and seasonal operational patterns all affect what normal looks like.
The workbench’s HELD/OPEN verdict records whether a control blocked the probe. It does not record what was logged or what an analyst would have seen. Monitoring and prevention are complementary; the workbench covers one side of that boundary.
Related¶
IT/OT boundary: the DMZ staging pattern for log collection discussed in the log collection section
Volt Typhoon: the Windows Event 4688 gap and its consequences
FrostyGoop: Modbus writes that protocol-aware monitoring could have surfaced
Ukraine grid incidents: the IEC 104 sessions a baselining monitor might have flagged